Industrial Solid State Relay HHG1
Parameters of Industrial Solid State Relay HHG1
Types | HHG1A-1/032F-38 100-250A(SSR-DA) | HHG1C-1/032F-120 100-250A(SSR-DA) |
Name | Single-phase Indusreial SSR | Single-phase Indusreial SSR |
Control Voltage | 014:3-14VDC,032:3-32VDC | 014:3-14VDC,032:3-32VDC |
Control Current | 5-35mA | 5-35mA |
Turn-on Voltage | 3VDC | 3VDC |
Turn-off Voltage | 1VDC | 1VDC |
Reverse Voltage | 32VDC | 32VDC |
Load Voltage | 38:40-440VAC | 120:60-1200VAC |
Load Current | 100A,120A,150A,200A,250A | 100A,120A,150A,200A,250A |
Transient Voltage | 38:1000VAC | 120:1600VAC |
On-state Voltage Drop | <1.6VAC | <1.6VAC |
On-off Time | ≤10ms | ≤10ms |
Off-state Leakage Current | ≤10mA | ≤10mA |
Dielectrics Voltage-resistance | ≥2500VAC | ≥2500VAC |
Insulation Resistance | 500mΩ 500VDC testing | 500mΩ 500VDC testing |
Ambient temperature | -30~80℃ | -30~80℃ |
Dimensions | 94L×34W×43H | 94L×34W×43H |
Work Pointer | LED | LED |
Installation | Fixed by Screw | Fixed by Screw |
Packing | Quantity | 120 |
Dimensions of outer case | 380×220×350mm |
Weight (each relay) | Approx. 235g |
Note:
1. When load currency is above 10A, a radiator is necessary; when above 80A, a fan is necessary.
2. When controlling inductive load, a varistor is necessary and its voltage could be 1.6-1.9 times of load voltage.
Outline drawing and Installation dimension (mm)