The NNG series of DC-AC single phase solid state relay adapts the international popular circuit and manufacture technique, which accord with the requirements of GB14048.5. The relay features strong compact structure, impact resistance, good shock resistance, no spark, no noise, high working reliability and long use age. The relay is used in the automatic control filed like signal light, scintillator, stage lighting control system, instrument and apparatus, medical equipment, copier, automatic washing machine, automatic fire equipment and security system, and it also can be used as the selector switch of the power capacitor which be compensated by the network power factor. In addition, the relay is widely used in the bad environment and frequent switching occasions like the chemical industry and coal industry which need prevent from explosion, damp, dust and erosion.
Load current | Heat sink model |
Below single phase 20A | NN-060 |
Below single phase 40A | NN-061 |
Below single phase 60A | NN-062 |
Below single phase 80A | NN-063 |
Below three-phase 20A | NN-035 |
Load current | Heat sink model |
Below three- phase 30A | NN-034 |
Below three- phase 40A | NN-036 |
Below three- phase 80A | NN-037 |
Below three- phase 150A | NN-038 |
Below three- phase 250A | NN-039 |
Load mode | Pure resistance | Heating wire | Incandescent lamp | Transformer |
Power factor | 1.0 | 0.7 | 0.5 | 0.4 |
Magnification times | 1.5 times | 2 times | 2.5 times | 4 times |
Load type | Electromagnet | Single phase motor | Three-phase motor | Capacitor switching |
Power factor | 0.5 | 0.2 | 0.3 | Surge current |
Magnification times | 4 times | 7 times | 6 times | 10 times |
Example 1: The user will choose the solid state relay with suitable ampere in the situation where the load mode is a heating wire load (power factor is 0.7) and practical working current is 10A?
According to the estimation method of attachment 2, we can conclude as follows:
10A(practical working current)× 2(magnification times)=20A
Therefore, the user should choose the solid state relay with 20A in this example.
Example 2: The user will choose the solid state relay with suitable ampere in the situation that load mode is single phase motor load(power factor is 0.2) and practical working current is 10A?
According to the estimation method of attachment 2, we can conclude as follows:
10A(practical working current)× 7(magnification times)=70A
Therefore, the user should choose the solid state relay with 70A in this example.
Clion offers its global customers a wide range of electronic switching devices with their high quality electromagnetic relays, solid state relays, solid state voltage regulators, and miniature snap action switches among a whole catalog of additional products. We have fully equipped automatic production and assembly lines as we offer superior quality electrically operated switches with thousands of models to choose from.
Index
relay switch, electric switch, switching device
Clion Electric Co.,Ltd.
Add.: No.319, Wei 18 Rd.,Yueqing Economic Development Zone,Yueqing City, Zhejiang Province, 325600
Contact Person: Tony Chen
Tel.: +86-577-57156992
Fax: +86-577-57572255
E-mail: clionrelay@hotmail.com